Surge & Arrester monitoring

SMC - Surge and Lightning Monitoring device

  • SMC  - Surge and Lightning Monitoring device
  • cvr2.jpg

Description

Streamer Electric has dedicated its research activities to lightning and surges qualification. This new range of products aims at helping our customer to understand the origin of surges, thier parameters and impact on equipment.

It involves diagnostic of metal oxide based surge arresters (MOR,TLA, MOA) in service, record peak currents, historical data, number of events, cumulative charges discharged by equipment.

It allows ageing and problems qualification to reach higher accuracy in order to optimize reliability and expenditure.

With a communication range of 2.5km LoRaWan standards allows the user have a safe and remote connection.

SM Series Surge Monitoring can be installed easily on ground conductors.Thanks to its IP65, housing, rugged materials and self power, the SM Series suitable for outdoors.

Power supply is ensured through supercap cell and solar panels. Optional DC power supply can also be arranged.


Key features

- Monitoring of surge arrester, EGLA, МОА, MOR, SPD, TLA.

- LoRa and NFC wireless solution. Wired via RS485, Digital output.

- Solar supply & external supply versions.

- Unique condition monitoring : resistive leakage current & total discharged energy monitoring system, lightning, surge events and discharges records.

- DuraЫe device: stainless steel, polycarbonate UV resistant, aluminum. Outdoor device : IP65.

- Up to 3 phases / surge arresters оп the same device.

- Monitoring software

- GPS localisation and timestamp


Technical characteristics

EARTHING CONNECТION

CONDUCТOR DIAMETER RANGE

5 to 25 1 35 to 300 mm2

INSTALLATION ON ТНЕ CONDUCТOR

Terminals, 13.5 mm hole in series

SURGE EVENT COUNTER

MINIMUM DISCHARGE РЕАК CURRENT DETECTED - 8/20 us waveform - IEC 62561-6

200 А

MAXIMUM DISCHARGE РЕАК CURRENT DETECTED - 10/350 us waveform - IEC 62561-6

100 kA

WAVEFORM REGISTRATION RESPONSE ТIМЕ

1,3 µs

MINIMUM TIME BETWEEN 2 STROKE FOR REGISTRATION, RESPONSE TIME

10 µs

LONG DURATION CURRENT WITHSTAND CAPABILIТ Y

2500 A for 4 ms

HIGH CURRENT WIТHSTAND CAPABILIТY

100 kA

IMPULSE CURRENT РЕАК MEASUREMENT

YES

IMPULSE DURATION/ IMPULSE POLARIТY

YES

MEASUREMENT

MINIMUM DISCHARGE РЕАК CURRENT MEASURED - 8/20 us waveform - IEC 62561-6

200 A

MAXIMUM DISCHARGE РЕАК CURRENT MEASURED - 10/350 us waveform - IEC 62561-6

40 kA

РЕАК LIGHTNING CURRENT ACCURACY 8/20us

10%

FOLLOW CURRENT / GROUND FAULT RANGE

70 to 10 000 A

FOLLOW CURRENT / GROUND FAULT (50/60Hz) ACCURACY

10%

ТОТАL LEFТ THROUGH l2t

YES

CHARGE RANGE

0 to 65C

LEAKAGE MEASUREMENTS

ТОТАL LEAKAGE CURRENT

50 µA to 50 mA

ACCURACY (at Tamb  ≤40 °С)

±10%

SURFACE POLLUTION & HUMIDIТY INGRESS DETECTION (UNDER EVALUATION)

YES

THIRD HARMONIC LEAKAGE CURRENT

50-5000 µA

ACCURACY (at Tamb ≤ 40 °С)

±15%

RESISTIVE LEAKAGE CURRENT

50-5000 µA

ACCURACY (at Tamb  ≤40 °С)

±15%



Installation








Please, fill in the form