LLPD d45z
This device is there to protect important networks from direct lightning strikes and back flashovers. Indented to be installed along the protected line, it works perfectly on distribution (sub-transmission) lines with the highest voltage of equipment up to 52 kV.
Operational principle
This product operates on the basis of EasyQuench technology.
d45z can easily be adapted to poles/towers of totally different configuration. This is possible due to various installation options.
Specifications
- Highest voltage for equipment, 52 kV
- Protects from Direct Lightning Strike
- Protects from Back Flashover
- No maintenance is required
Parameters of product
Electrical line parameters
Highest voltage for equipment*, kV | 52 |
Maximum prospective fault current, kA | 5 |
External air gap, mm | 80+80 |
50% flashover voltage, kV (80+80 mm air gap) | <280 |
Power frequency withstand voltage**, kV (wet/dry) | 95/95 |
Lightning parameters
Lightning discharge capability (200 μs)***, C | 2.8 |
High current impulse (4/10 μs), kA | 65 |
Maximum quenching lightning current, kA | 20 (8/50µs) |
Minimum withstand amount of operations | 10 |
General Parameters
Additional power losses on the line, % | 0 |
Average expected lifespan, years | 30 |
UV resistance****, h | 1000 |
Weight, kg | 7 |
Maintenance | 1 visual verification/ year |
* According to IEC 60038, ** According to IEC 60071-1, *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
Installation
Tension insulation
Suspension insulation