Lightning protection

LLPD d45z up to 52 kV (DLS)

  • Protection against DLS, BFO
  • Highest voltage for equipment, kV 52
  • Maximum prospective fault current, kA 5.0
  • Lightning discharge capability, C 2.8
  • Installation 1, 2 or 3 pcs per pole
  • LLPD d45z up to 52 kV (DLS)
  • LLPD d45z up to 52 kV (DLS)
  • LLPD d45z.png
  • 28272da62a49d468ba7b03ce31bb1128.png

LLPD d45z

This device is there to protect important networks from direct lightning strikes and back flashovers. Indented to be installed along the protected line, it works perfectly on distribution (sub-transmission) lines with the highest voltage of equipment up to 52 kV.

Operational principle

This product operates on the basis of EasyQuench technology.

d45z can easily be adapted to poles/towers of totally different configuration. This is possible due to various installation options.

Specifications 

  • Highest voltage  for equipment, 52 kV
  • Protects from Direct Lightning Strike
  • Protects from Back Flashover
  • No maintenance is required

Parameters of product

Electrical line parameters

Highest voltage for equipment*, kV 52
Maximum prospective fault current, kA 5
External air gap, mm 80+80
50% flashover voltage, kV (80+80 mm air gap) <280
Power frequency withstand voltage**,  kV (wet/dry) 95/95

Lightning parameters

    Lightning discharge capability  (200 μs)***, C 2.8
     High current impulse (4/10 μs), kA 65
     Maximum quenching lightning current,  kA 20  (8/50µs)
     Minimum withstand amount of operations 10

General Parameters 

Additional power losses on the line, % 0
Average expected lifespan, years 30
 UV resistance****, h 1000
 Weight, kg 7
  Maintenance 1 visual verification/  year


* According to IEC 60038, ** According to IEC 60071-1, *** According to  IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217